| Specification | RWSTS-3363A/4P |
| Rated Current | 63A |
| Capacity | 41.5KW |
| Transfer Time | ≤5ms SCR transfer (no load interruption) |
| Input Parameters | |
| Input Mode | Dual-source input, in-phase or out-of-phase |
| Input Interface | Feed-through terminal block (with cooling fan) |
| Input Voltage | 340~420V (configurable) |
| Input Frequency | 50Hz-60Hz |
| Output Parameters | |
| Output Voltage | 380V± 10% |
| Output Interface | Feed-through terminal block |
| Overload Capacity | 110% |
| Output Efficiency | >98% |
| Communication and Alarms | |
| Display | LCD display of electrical parameters and status; LED status and fault indication |
| Audible Alarm | Dual-input undervoltage protection, overvoltage protection, power-loss alarm, output overcurrent alarm |
| Communication | RS232 serial port (default) / RS485 serial port / dry contacts |
| Protection Functions | |
| Input Protection | Overcurrent, undervoltage, overvoltage and power-loss protection |
| Output Protection | Overcurrent protection, transfer short-circuit protection |
| Operating Environment | |
| Ambient Temperature | -30°C~60°C |
| Ambient Humidity | 0~90% |
| Noise | ≤40 db |
| Physical Specifications | |
| Dimensions (mm) | 420*430*350mm (W*D*H) |
| Weight (kg) | 38kg |