Kehua
Kehua YTR33100
Kehua YTR33100
- Capacity
- 100KVA
- In / Out
- 3-Phase In / 3-Phase Out (380V:380V)
Price on requestView details

Kehua
Kehua YTR3350
| Input voltage range (Vac) | 80Vac~280Vac |
| Input frequency range (Hz) | 40-70Hz |
| Bypass Sync Tracking Range (Hz) | 50/60±10% |
| Bypass Input Voltage Range (Vac) | -15%(10/20/25 optional)/-20%(15/30/40/50/60 optional) |
| Input power factor | ≥0.99 |
| Battery (VDC) | ±180 to ±240 (adjustable number of battery cells) |
| Voltage (Vac) | L-L:380/400/415±1% |
| Frequency (Hz) | When utility power is normal, the bypass input is tracked; when utility power is abnormal, the unit operates at 50±0.1Hz or 60±0.1 Hz. |
| three-phase phase error | Three-phase with balanced rated resistive load ≤1° |
| Waveform distortion (THDv) | ≤1% (resistive full load) |
| Maximum system efficiency | 96% |
| Overload capacity | <105% load for long-term operation, 105%~ 115% load for 60min,116%~ 130% load for 10min,131%~ 150% load for 1min |
| Manual Maintenance Bypass | Maintenance bypass switch with no changeover time |
| DC start function | Possess |
| Communication function | Dry contact, RS485, MODBUS, SNMP (optional) |
| Alert feature | Abnormal input, low battery voltage, overload, fault, etc. |
| Protection function | Output short circuit protection, output overvoltage/undervoltage protection, overload protection, over temperature protection, battery undervoltage protection, etc. |
| Noise (dB) | <65 (one meter from the front of the box) |
| Operating temperature (℃) | 0~40 |
| Size (width * depth * height)(mm)) | 450*840*967 |
| Weight (kg) | 160 |
Leave your details and an engineer will get back to you within one business day.
UPS Power Supply

Kehua
Kehua YTR33100

Kehua
Kehua YTM33125

Kehua
Kehua YTR33200

Kehua
Kehua YTR3360

Kehua
Kehua YTR3320

Kehua
Kehua YTR3340

Kehua
Kehua YTR33160

Kehua
Kehua YTR3380