UPS Runtime Configuration
30KVA UPS — 8-hour backup configuration

Matching UPS
Emerson Adapt-PM-30KVA-150K frame
Plan 1Long machine 30KVA 8 hour hour configuration scheme Y = 500
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-30KVA-150K Framework
- Emerson
- 1
- 1*450.00kg
- 1000*1000*2000mm
- 123,379.00
- 123,379.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 5 groups 200 yuan
- 200*30.50kg
- 330*171*214mm
- 1,638.00
- 327,600.00
- battery cabinet:
- RC40
- Ruiwu
- 5 groups
- 5*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 201 root
- 201*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- Group 6
- 0kg
- 6*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 200 pieces
- 6,500.00
- Logistics transportation fee
- 3325.00
- 3325.00
- In-place fee
- 6750.00
- 6750.00
Total: 6,550.00kg 467,554.00.00Scenario Download (Execl)Submit order
Installation parameters
30KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 10mm2 |
| Input neutral conductor size | 16mm2 |
| Input earth conductor size | 16mm2 |
| Input breaker | 63A -3P |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 10mm2 |
| Output neutral conductor size | 16mm2 |
| Output earth conductor size | 16mm2 |
| Output breaker | 63A-3P |
| Battery specifications | |
| External battery breaker | 150A-3P |
| External battery cable size | 10mm2 |