UPS Runtime Configuration
40KVA UPS — 4-hour backup configuration

Matching UPS
Emerson NX-40KVA
Plan 1Long machine 40KVA 4 hour configuration scheme Y = 333
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson NX-40KVA
- Emerson
- 1
- 1*210.00kg
- 600*850*1600mm
- 81,318.00
- 81,318.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 4 groups 160 block
- 160*30.50kg
- 330*171*214mm
- 1,638.00
- 262,080.00
- battery cabinet:
- RC40
- Ruiwu
- 4 groups
- 4*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 25 square battery connection line
- Ruiwu
- 161 root
- 161*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_100A
- Schneider Electric
- 5 groups
- 1.60kg
- 5*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 160 only
- 5,700.00
- Logistics transportation fee
- 2599.00
- 2599.00
- In-place fee
- 5298.00
- 5298.00
Total: 5,098.00kg 356,995.00.00Scenario Download (Execl)Submit order
Installation parameters
40KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 10mm2 |
| Input neutral conductor size | 35mm2 |
| Input earth conductor size | 35mm2 |
| Input breaker | 80A -3P |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 10mm2 |
| Output neutral conductor size | 35mm2 |
| Output earth conductor size | 35mm2 |
| Output breaker | 100A -3P |
| Battery specifications | |
| External battery breaker | 200A-3P |
| External battery cable size | 10mm2 |