Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

30KVA UPS — 1-hour backup configuration

Rated power
30KVA
Backup time
1 h
Emerson UHA3R-0300L

Matching UPS

Emerson UHA3R-0300L

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 30KVA 1 hour hour configuration scheme Y = 78
  • Host:Emerson UHA3R-0300L
  • Empty opening:NSX100F_DC_3P_100A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC32

    Quantity: 1
    Battery:Emerson (Vertiv)U12V230L/A

    Quantity: 1 group of 32 pieces
    Connection line:25 square battery connection line

    Number of: 33
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • battery cabinet:
  • RC32
  • Love Pace
  • Group 1
  • 1*0.00kg
  • 828*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 32.
  • 3,140.00

Total: 755.60kg 4,524.00.00Scenario Download (Execl)Submit order

Installation parameters

30KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 10mm2
Input neutral conductor size 16mm2
Input earth conductor size 16mm2
Input breaker 63A -3P
Output parameter
Output voltage 380V AC
Output conductor size 10mm2
Output neutral conductor size 16mm2
Output earth conductor size 16mm2
Output breaker 63A-3P
Battery specifications
External battery breaker 150A-3P
External battery cable size 10mm2