UPS Runtime Configuration
30KVA UPS — 8-hour backup configuration

Matching UPS
Delta GES-HPH-30K
Plan 1Long machine 30KVA 8 hour hour configuration scheme Y = 1000
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Delta GES-HPH-30K
- Delta
- 1
- 1*86.50kg
- 380*800*800mm
- 42,600.00
- 42,600.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 10 groups 200 yuan
- 200*30.50kg
- 330*171*214mm
- 1,638.00
- 327,600.00
- battery cabinet:
- RC20
- Ruiwu
- 10 groups
- 10*0.00kg
- 1002*499*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 25 square battery connection line
- Ruiwu
- 201 root
- 201*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_100A
- Schneider Electric
- Group 11
- 1.60kg
- 11*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 200 pieces
- 6,500.00
- Logistics transportation fee
- 3152.00
- 3152.00
- In-place fee
- 6404.00
- 6404.00
Total: 6,204.10kg 386,256.00.00Scenario Download (Execl)Submit order
Installation parameters
30KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 10mm2 |
| Input neutral conductor size | 16mm2 |
| Input earth conductor size | 16mm2 |
| Input breaker | 63A -3P |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 10mm2 |
| Output neutral conductor size | 16mm2 |
| Output earth conductor size | 16mm2 |
| Output breaker | 63A-3P |
| Battery specifications | |
| External battery breaker | 150A-3P |
| External battery cable size | 10mm2 |