UPS Runtime Configuration
5KVA UPS — 2-hour backup configuration

Matching UPS
Delta GES-RT5KS
Plan 1Long machine 5KVA 2 hour configuration scheme Y = 52
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Delta GES-RT5KS
- Delta
- 1
- 1*15.50kg
- 440*671*89mm
- 6,050.00
- 6,050.00
- Battery:
- Ruiwu RW-G-12-65
- Ruiwu
- Group 1 16 pieces
- 16*21.00kg
- 350*166*179mm
- 1,128.00
- 18,048.00
- battery cabinet:
- RC16
- Ruiwu
- Group 1
- 1*0.00kg
- 828*499*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 6 square battery connection line
- Ruiwu
- 17 pieces
- 17*0.00kg
- Standard
- 6.00
- 102.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 1000.00
- 1 unit
- 1,000.00
- Battery installation fee
- 20.00
- 16 only.
- 1,320.00
- Logistics transportation fee
- 226.00
- 226.00
- In-place fee
- 553.00
- 553.00
Total: 352.70kg 26,299.00.00Scenario Download (Execl)Submit order
Installation parameters
5KVA AC 220V input: AC 220V output
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 4mm2 |
| Input neutral conductor size | 4mm2 |
| Input earth conductor size | 4mm2 |
| Input breaker | 32A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 4mm2 |
| Output neutral conductor size | 4mm2 |
| Output earth conductor size | 4mm2 |
| Output breaker | 32A -2P |
| Battery specifications | |
| External battery breaker | 75A-2P |
| External battery cable size | 6mm2 |