UPS Runtime Configuration
50KVA UPS — 30-minute backup configuration

Matching UPS
Kehua FR-UK3150
Plan 1Long machine 50KVA 0.5 hour configuration scheme Y = 72
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua FR-UK3150
- Kehua UPS power supply
- 1
- 1*304.00kg
- 400*800*1180mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-65
- Ruiwu
- Group 1 29 pieces
- 29*21.00kg
- 350*166*179mm
- 1,128.00
- 32,712.00
- battery cabinet:
- No matching battery cabinet
- Group 1
- 1*0kg
- mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 50 square battery connection line
- Ruiwu
- 30 pieces
- 30*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_2P_32A
- Schneider Electric
- Group 1
- 1.20kg
- 1*161*70*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 29.
- 3,080.00
- Logistics transportation fee
- 507.00
- 507.00
- In-place fee
- 1114.00
- 1114.00
Total: 914.20kg 37,413.00.00Scenario Download (Execl)Submit order
Installation parameters
50KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 25mm2 |
| Input neutral conductor size | 50mm2 |
| Input earth conductor size | 25mm2 |
| Input breaker | 150a -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 25mm2 |
| Output neutral conductor size | 50mm2 |
| Output earth conductor size | 25mm2 |
| Output breaker | 150a -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 300A-Input AC 380V: Output AC 380V |
| External battery cable size | 50mm2 |