UPS Runtime Configuration
120KVA UPS — 30-minute backup configuration

Matching UPS
Emerson Adapt-PM-120KVA-150K frame
Plan 1Long machine 120KVA 0.5 hour configuration scheme Y = 125
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-120KVA-150K Framework
- Emerson
- 1
- 1*450.00kg
- 600*1100*2000mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- Group 1 40 pieces
- 40*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- RC40
- Love Pace
- Group 1
- 1*0.00kg
- 1002*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 120 square battery connection line
- Ruiwu
- 41
- 41*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX400FDC
- Schneider Electric
- Group 1
- 6.00kg
- 1*255*185*110mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 40 only
- 5,800.00
- Logistics transportation fee
- 848.00
- 848.00
- In-place fee
- 1796.00
- 1796.00
Total: 1,596.00kg 8,444.00.00Scenario Download (Execl)Submit order
Installation parameters
120KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 120mm2 |
| Input neutral conductor size | 120mm2 |
| Input earth conductor size | 50mm2 |
| Input breaker | 250A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 95mm2 |
| Output neutral conductor size | 95mm2 |
| Output earth conductor size | 50mm2 |
| Output breaker | 200A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 200A-Input AC 380V: Output AC 380V |
| External battery cable size | 95mm2 |