UPS Runtime Configuration
180KVA UPS — 8-hour backup configuration

Matching UPS
Emerson Adapt-PM-180KVA-300K frame
Plan 1Long machine 180KVA 8 hour hour configuration scheme Y = 3000
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-180KVA-300K Framework
- Emerson
- 1
- 1*670.00kg
- 1200*1100*2000mm
- 536,803.00
- 536,803.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group of 30 1200 block
- 1200*30.50kg
- 330*171*214mm
- 1,638.00
- 1,965,600.00
- battery cabinet:
- RC40
- Ruiwu
- Group of 30
- 30*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 25 square battery connection line
- Ruiwu
- 1201 root
- 1201*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_100A
- Schneider Electric
- Group 31
- 1.60kg
- 31*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 1200 only
- 29,000.00
- Logistics transportation fee
- 18710.00
- 18710.00
- In-place fee
- 37520.00
- 37520.00
Total: 37,319.60kg 2,587,633.00.00Scenario Download (Execl)Submit order
Installation parameters
180KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 160mm2 |
| Input neutral conductor size | 160mm2 |
| Input earth conductor size | 160mm2 |
| Input breaker | 500A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 150mm2 |
| Output neutral conductor size | 150mm2 |
| Output earth conductor size | 150mm2 |
| Output breaker | 400A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 600A-Input AC 380V: Output AC 380V |
| External battery cable size | 250mm2 |