Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

18KVA UPS — 30-minute backup configuration

Rated power
18KVA
Backup time
30 min
Emerson Adapt-PM-18KVA-90K frame

Matching UPS

Emerson Adapt-PM-18KVA-90K frame

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 18KVA 0.5 hour configuration scheme Y = 19
  • Host:Emerson Adapt-PM-18KVA-90K Framework
  • Empty opening:NSX250F_DC_3P_200A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC20

    Quantity: 1
    Battery:Eaton ETNHF12-75W

    Quantity: 1 group of 40 pieces
    Connection line:50 square battery connection line

    Number of: 41
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Eaton ETNHF12-75W
  • Eaton Battery
  • Group 1    40 pieces
  • 40*8.10kg
  • 166*175*125mm
  • 0.00
  • 0.00
  • battery cabinet:
  • RC20
  • Love Pace
  • Group 1
  • 1*0.00kg
  • 1002*499*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 40 only
  • 1,800.00

Total: 665.90kg 3,049.00.00Scenario Download (Execl)Submit order

Installation parameters

18KVA input AC 380V: output AC 220V
Input parameter
Input voltage 380V AC
Input live conductor size 4mm2
Input neutral conductor size 10mm2
Input earth conductor size 4mm2
Input breaker 50A -Input AC 380V: Output AC 220V
Output parameter
Output voltage 380V AC
Output conductor size 4mm2
Output neutral conductor size 10mm2
Output earth conductor size 4mm2
Output breaker 50A -Input AC 380V: Output AC 220V
Battery specifications
External battery breaker 125A-Input AC 380V: Output AC 220V
External battery cable size 4mm2

18KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 4mm2
Input neutral conductor size 10mm2
Input earth conductor size 4mm2
Input breaker 50A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 380V AC
Output conductor size 4mm2
Output neutral conductor size 10mm2
Output earth conductor size 4mm2
Output breaker 50A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 125A-Input AC 380V: Output AC 380V
External battery cable size 4mm2