UPS Runtime Configuration
80KVA UPS — 1-hour backup configuration

Matching UPS
Emerson UL33-0800L
Plan 1Long machine 80KVA 1 hour hour configuration scheme Y = 222
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson UL33-0800L
- Emerson
- 1
- 1*790.00kg
- 900*850*1900mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- Group 2 60 yuan
- 60*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- No matching battery cabinet
- Group 2
- 2*0kg
- mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 50 square battery connection line
- Ruiwu
- 61
- 61*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX250F_DC_3P_200A
- Schneider Electric
- Group 3
- 1.90kg
- 3*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 60 only.
- 3,700.00
- Logistics transportation fee
- 1303.00
- 1303.00
- In-place fee
- 2706.00
- 2706.00
Total: 2,505.70kg 7,709.00.00Scenario Download (Execl)Submit order
Installation parameters
80KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 35mm2 |
| Input neutral conductor size | 95mm2 |
| Input earth conductor size | 35mm2 |
| Input breaker | 175A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 35mm2 |
| Output neutral conductor size | 95mm2 |
| Output earth conductor size | 35mm2 |
| Output breaker | 175A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 400A-Input AC 380V: Output AC 380V |
| External battery cable size | 95mm2 |