Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

100KVA UPS — 2-hour backup configuration

Rated power
100KVA
Backup time
2 h
Emerson UL33-1000L

Matching UPS

Emerson UL33-1000L

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 100KVA 2 hour configuration scheme Y = 556
  • Host:Emerson UL33-1000L
  • Empty opening:NSX250F_DC_3P_250A

    Quantity: 7

    Battery DC switch cabinet
  • battery cabinet:No matching battery cabinet

    Quantity: 6
    Battery:Ruiwu RW-G-12-100

    Quantity: 6 groups of 180 blocks
    Connection line:95 square battery connection line

    Quantity: 181
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 6    180 block
  • 180*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 294,840.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 180 only
  • 8,600.00

Total: 6,293.30kg 451,167.00.00Scenario Download (Execl)Submit order

Installation parameters

100KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 120mm2
Input neutral conductor size 120mm2
Input earth conductor size 50mm2
Input breaker 250A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 380V AC
Output conductor size 95mm2
Output neutral conductor size 95mm2
Output earth conductor size 50mm2
Output breaker 200A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 200A-Input AC 380V: Output AC 380V
External battery cable size 95mm2