Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

40KVA UPS — 8-hour backup configuration

Rated power
40KVA
Backup time
8 h
Delta GES-HPH-40K

Matching UPS

Delta GES-HPH-40K

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 40KVA 8 hour hour configuration scheme Y = 1333
  • Host:Delta GES-HPH-40K
  • Empty opening:NSX100F_DC_3P_100A

    Quantity: 15

    Battery DC switch cabinet
  • battery cabinet:RC20

    Number of: 14
    Battery:Ruiwu RW-G-12-100

    Quantity: 14 groups of 280 blocks
    Connection line:25 square battery connection line

    Quantity: 281
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 14    280 block
  • 280*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 458,640.00
  • battery cabinet:
  • RC20
  • Ruiwu
  • Group 14
  • 14*0.00kg
  • 1002*499*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 280 only
  • 8,100.00

Total: 8,650.50kg 526,445.00.00Scenario Download (Execl)Submit order

Installation parameters

40KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 10mm2
Input neutral conductor size 35mm2
Input earth conductor size 35mm2
Input breaker 80A -3P
Output parameter
Output voltage 380V AC
Output conductor size 10mm2
Output neutral conductor size 35mm2
Output earth conductor size 35mm2
Output breaker 100A -3P
Battery specifications
External battery breaker 200A-3P
External battery cable size 10mm2