Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

80KVA UPS — 30-minute backup configuration

Rated power
80KVA
Backup time
30 min
Delta GES-HPH-80K

Matching UPS

Delta GES-HPH-80K

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 80KVA 0.5 hour configuration scheme Y = 104
  • Host:Delta GES-HPH-80K
  • Empty opening:NSX250F_DC_3P_200A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC32

    Quantity: 1
    Battery:Eaton ETNHF12-390WP

    Quantity: 1 group of 32 pieces
    Connection line:50 square battery connection line

    Number of: 33
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Eaton ETNHF12-390WP
  • Eaton Battery
  • Group 1    32 blocks
  • 32*28.50kg
  • 339*170*220mm
  • 0.00
  • 0.00
  • battery cabinet:
  • RC32
  • Love Pace
  • Group 1
  • 1*0.00kg
  • 828*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 32.
  • 3,140.00

Total: 1,106.40kg 5,049.00.00Scenario Download (Execl)Submit order

Installation parameters

80KVA input AC 380V: output AC 380V
Input parameter
Input voltage 220V AC
Input live conductor size 35mm2
Input neutral conductor size 95mm2
Input earth conductor size 35mm2
Input breaker 175A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 220V AC
Output conductor size 35mm2
Output neutral conductor size 95mm2
Output earth conductor size 35mm2
Output breaker 175A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 400A-Input AC 380V: Output AC 380V
External battery cable size 95mm2