UPS Runtime Configuration
10KVA UPS — 30-minute backup configuration

Matching UPS
Santak C10KS
Plan 1Long machine 10KVA 0.5 hours configuration scheme Y = 26
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Santak C10KS
- Santak
- 1
- 1*16.00kg
- 500*212*420mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-75W
- Eaton Battery
- Group 1 16 pieces
- 16*8.10kg
- 166*175*125mm
- 0.00
- 0.00
- battery cabinet:
- RC8
- Love Pace
- Group 1
- 1*0.00kg
- 828*499*572mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 10 square battery connection line
- Ruiwu
- 17 pieces
- 17*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_32A
- Schneider Electric
- Group 1
- 1.60kg
- 1*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 1000.00
- 1 unit
- 1,000.00
- Battery installation fee
- 20.00
- 16 only.
- 1,320.00
- Logistics transportation fee
- 124.00
- 124.00
- In-place fee
- 347.00
- 347.00
Total: 147.20kg 1,791.00.00Scenario Download (Execl)Submit order
Installation parameters
10KVA AC 220V input: AC 220V output
10KVA input AC 380V: output AC 220V
10KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 6mm2 |
| Input neutral conductor size | 6mm2 |
| Input earth conductor size | 6mm2 |
| Input breaker | 40A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 6mm2 |
| Output neutral conductor size | 6mm2 |
| Output earth conductor size | 6mm2 |
| Output breaker | 40A -2P |
| Battery specifications | |
| External battery breaker | 100A-2P |
| External battery cable size | 10mm2 |
10KVA input AC 380V: output AC 220V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 6mm2 |
| Input neutral conductor size | 6mm2 |
| Input earth conductor size | 6mm2 |
| Input breaker | 40A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 6mm2 |
| Output neutral conductor size | 6mm2 |
| Output earth conductor size | 6mm2 |
| Output breaker | 40A -2P |
| Battery specifications | |
| External battery breaker | 100A-2P |
| External battery cable size | 10mm2 |
10KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 6mm2 |
| Input neutral conductor size | 6mm2 |
| Input earth conductor size | 6mm2 |
| Input breaker | 40A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 6mm2 |
| Output neutral conductor size | 6mm2 |
| Output earth conductor size | 6mm2 |
| Output breaker | 40A -3P |
| Battery specifications | |
| External battery breaker | 100A-3P |
| External battery cable size | 10mm2 |







