Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

6KVA UPS — 2-hour backup configuration

Rated power
6KVA
Backup time
2 h
Emerson ITA-06k00AL1102C00

Matching UPS

Emerson ITA-06k00AL1102C00

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 6KVA 2 hour configuration scheme Y = 62
  • Host:Emerson ITA-06k00AL1102C00
  • Empty opening:NSX100F_DC_2P_50A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC16

    Quantity: 1
    Battery:Ruiwu RW-G-12-65

    Quantity: 1 group of 16 pieces
    Connection line:6 square battery connection line

    Quantity: 17
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-65
  • Ruiwu
  • Group 1    16 pieces
  • 16*21.00kg
  • 350*166*179mm
  • 1,128.00
  • 18,048.00
  • battery cabinet:
  • RC16
  • Ruiwu
  • Group 1
  • 1*0.00kg
  • 828*499*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 16 only.
  • 1,320.00

Total: 348.20kg 28,413.00.00Scenario Download (Execl)Submit order

Installation parameters

6KVA AC 220V input: AC 220V output
Input parameter
Input voltage 220V AC
Input live conductor size 4mm2
Input neutral conductor size 4mm2
Input earth conductor size 4mm2
Input breaker 32A -2P
Output parameter
Output voltage 220V AC
Output conductor size 4mm2
Output neutral conductor size 4mm2
Output earth conductor size 4mm2
Output breaker 32A -2P
Battery specifications
External battery breaker 75A-2P
External battery cable size 6mm2