UPS Runtime Configuration
200KVA UPS — 1-hour backup configuration

Matching UPS
Emerson eXM-200KVA
Plan 1Long machine 200KVA 1 hour hour configuration scheme Y = 417
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson eXM-200KVA
- Emerson
- 1
- 1*520.00kg
- 600*1000*2000mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- 4 groups 160 block
- 160*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- RC40
- Love Pace
- 4 groups
- 4*0.00kg
- 1002*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 240 square battery connection line
- Ruiwu
- 161 root
- 161*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX630FDC
- Schneider Electric
- 5 groups
- 6.00kg
- 5*255*140*110mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 160 only
- 8,200.00
- Logistics transportation fee
- 2605.00
- 2605.00
- In-place fee
- 5310.00
- 5310.00
Total: 5,110.00kg 16,115.00.00Scenario Download (Execl)Submit order
Installation parameters
200KVA 3:3
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 160mm2 |
| Input neutral conductor size | 160mm2 |
| Input earth conductor size | 160mm2 |
| Input breaker | 500A -3:3 |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 150mm2 |
| Output neutral conductor size | 150mm2 |
| Output earth conductor size | 150mm2 |
| Output breaker | 400A -3:3 |
| Battery specifications | |
| External battery breaker | 600A-3:3 |
| External battery cable size | 250mm2 |