UPS Runtime Configuration
100KVA UPS — 4-hour backup configuration

Matching UPS
Emerson Adapt-PM-100KVA-250K frame
Plan 1Long machine 100KVA 4 hours configuration scheme Y = 833
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-100KVA-250K Framework
- Emerson
- 1
- 1*400.00kg
- 1000*1000*2000mm
- 318,556.00
- 318,556.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 9 360 block
- 360*30.50kg
- 330*171*214mm
- 1,638.00
- 589,680.00
- battery cabinet:
- RC40
- Ruiwu
- Group 9
- 9*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 361 root
- 361*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- 10 groups
- 0kg
- 10*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 360 only
- 12,200.00
- Logistics transportation fee
- 5740.00
- 5740.00
- In-place fee
- 11580.00
- 11580.00
Total: 11,380.00kg 937,756.00.00Scenario Download (Execl)Submit order
Installation parameters
100KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 120mm2 |
| Input neutral conductor size | 120mm2 |
| Input earth conductor size | 50mm2 |
| Input breaker | 250A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 95mm2 |
| Output neutral conductor size | 95mm2 |
| Output earth conductor size | 50mm2 |
| Output breaker | 200A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 200A-Input AC 380V: Output AC 380V |
| External battery cable size | 95mm2 |