Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

200KVA UPS — 8-hour backup configuration

Rated power
200KVA
Backup time
8 h
Emerson Adapt-PM-200KVA-250K frame

Matching UPS

Emerson Adapt-PM-200KVA-250K frame

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 200KVA 8 hour hour configuration scheme Y = 3333
  • Host:Emerson Adapt-PM-200KVA-250K Framework
  • Empty opening:No matching DC open

    Number of: 35

    Battery DC switch cabinet
  • battery cabinet:RC40

    Number of: 34
    Battery:Ruiwu RW-G-12-100

    Quantity: 34 groups of 1360 blocks
    Connection line:No matching battery cable

    Quantity: 1361
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 34    1360 block
  • 1360*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 2,227,680.00
  • battery cabinet:
  • RC40
  • Ruiwu
  • Group 34
  • 34*0.00kg
  • 0*0*0mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 1360 only
  • 32,200.00

Total: 41,980.00kg 2,816,876.00.00Scenario Download (Execl)Submit order

Installation parameters

200KVA 3:3
Input parameter
Input voltage 380V AC
Input live conductor size 160mm2
Input neutral conductor size 160mm2
Input earth conductor size 160mm2
Input breaker 500A -3:3
Output parameter
Output voltage 380V AC
Output conductor size 150mm2
Output neutral conductor size 150mm2
Output earth conductor size 150mm2
Output breaker 400A -3:3
Battery specifications
External battery breaker 600A-3:3
External battery cable size 250mm2