UPS Runtime Configuration
200KVA UPS — 8-hour backup configuration

Matching UPS
Emerson Adapt-PM-200KVA-250K frame
Plan 1Long machine 200KVA 8 hour hour configuration scheme Y = 3333
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-200KVA-250K Framework
- Emerson
- 1
- 1*500.00kg
- 1000*1000*2000mm
- 493,776.00
- 493,776.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 34 1360 block
- 1360*30.50kg
- 330*171*214mm
- 1,638.00
- 2,227,680.00
- battery cabinet:
- RC40
- Ruiwu
- Group 34
- 34*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 1361 root
- 1361*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- Group of 35
- 0kg
- 35*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 1360 only
- 32,200.00
- Logistics transportation fee
- 21040.00
- 21040.00
- In-place fee
- 42180.00
- 42180.00
Total: 41,980.00kg 2,816,876.00.00Scenario Download (Execl)Submit order
Installation parameters
200KVA 3:3
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 160mm2 |
| Input neutral conductor size | 160mm2 |
| Input earth conductor size | 160mm2 |
| Input breaker | 500A -3:3 |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 150mm2 |
| Output neutral conductor size | 150mm2 |
| Output earth conductor size | 150mm2 |
| Output breaker | 400A -3:3 |
| Battery specifications | |
| External battery breaker | 600A-3:3 |
| External battery cable size | 250mm2 |