UPS Runtime Configuration
450KVA UPS — 2-hour backup configuration

Matching UPS
Emerson Adapt-PM-450KVA-600K frame
Plan 1Long machine 450KVA 2 hour configuration scheme Y = 1875
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-450KVA-600K Framework
- Emerson
- 1
- 1*945.00kg
- 1800*1000*2000mm
- 1,296,440.00
- 1,296,440.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 19 760 block
- 760*30.50kg
- 330*171*214mm
- 1,638.00
- 1,244,880.00
- battery cabinet:
- RC40
- Ruiwu
- Group 19
- 19*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 761 root
- 761*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- 20 groups
- 0kg
- 20*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 760 only
- 20,200.00
- Logistics transportation fee
- 12112.00
- 12112.00
- In-place fee
- 24325.00
- 24325.00
Total: 24,125.00kg 2,597,957.00.00Scenario Download (Execl)Submit order
Installation parameters
450KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 300mm2 |
| Input neutral conductor size | 300mm2 |
| Input earth conductor size | 300mm2 |
| Input breaker | 1000A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 250mm2 |
| Output neutral conductor size | 250mm2 |
| Output earth conductor size | 250mm2 |
| Output breaker | 800A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 1200A-Input AC 380V: Output AC 380V |
| External battery cable size | 450mm2 |






