Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

550KVA UPS — 2-hour backup configuration

Rated power
550KVA
Backup time
2 h
Emerson Adapt-PM-550KVA-600K frame

Matching UPS

Emerson Adapt-PM-550KVA-600K frame

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 550KVA 2 hour hour configuration scheme Y = 2292
  • Host:Emerson Adapt-PM-550KVA-600K Framework
  • Empty opening:No matching DC open

    Quantity: 24

    Battery DC switch cabinet
  • battery cabinet:RC40

    Number of: 23
    Battery:Ruiwu RW-G-12-100

    Quantity: 23 groups of 920 blocks
    Connection line:No matching battery cable

    Quantity: 921
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 23    920 block
  • 920*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 1,506,960.00
  • battery cabinet:
  • RC40
  • Ruiwu
  • Group 23
  • 23*0.00kg
  • 0*0*0mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 920 only
  • 23,400.00

Total: 29,075.00kg 3,045,882.00.00Scenario Download (Execl)Submit order

Installation parameters

550KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 400mm2
Input neutral conductor size 400mm2
Input earth conductor size 400mm2
Input breaker 1250A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 380V AC
Output conductor size 350mm2
Output neutral conductor size 350mm2
Output earth conductor size 350mm2
Output breaker 1000A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 1600A-Input AC 380V: Output AC 380V
External battery cable size 600mm2