UPS Runtime Configuration
40KVA UPS — 1-hour backup configuration

Matching UPS
Ruiwu HF33040
Plan 1Long machine 40KVA 1 hour hour configuration scheme Y = 104
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Ruiwu HF33040
- Ruiwu
- 1
- 1*156.00kg
- 600*778*1200mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- Group 1 32 blocks
- 32*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- RC32
- Love Pace
- Group 1
- 1*0.00kg
- 828*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 25 square battery connection line
- Ruiwu
- 33 pieces
- 33*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_100A
- Schneider Electric
- Group 1
- 1.60kg
- 1*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 32.
- 3,140.00
- Logistics transportation fee
- 585.00
- 585.00
- In-place fee
- 1270.00
- 1270.00
Total: 1,069.60kg 4,995.00.00Scenario Download (Execl)Submit order
Installation parameters
40KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 10mm2 |
| Input neutral conductor size | 35mm2 |
| Input earth conductor size | 35mm2 |
| Input breaker | 80A -3P |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 10mm2 |
| Output neutral conductor size | 35mm2 |
| Output earth conductor size | 35mm2 |
| Output breaker | 100A -3P |
| Battery specifications | |
| External battery breaker | 200A-3P |
| External battery cable size | 10mm2 |







