Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

200KVA UPS — 1-hour backup configuration

Rated power
200KVA
Backup time
1 h
Ruiwu HF33200

Matching UPS

Ruiwu HF33200

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 200KVA 1 hour hour configuration scheme Y = 417
  • Host:Ruiwu HF33200
  • Empty opening:NSX630FDC

    Number of: 5

    Battery DC switch cabinet
  • battery cabinet:RC40

    Number of: 4
    Battery:Eaton ETNHF12-390WP

    Quantity: 4 groups of 160 blocks
    Connection line:240 square battery connection line

    Quantity: 161
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Eaton ETNHF12-390WP
  • Eaton Battery
  • 4 groups    160 block
  • 160*28.50kg
  • 339*170*220mm
  • 0.00
  • 0.00
  • battery cabinet:
  • RC40
  • Love Pace
  • 4 groups
  • 4*0.00kg
  • 1002*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • DC air on:
  • NSX630FDC
  • Schneider Electric
  • 5 groups
  • 6.00kg
  • 5*255*140*110mm
  • 0.00
  • 0.00

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 160 only
  • 8,200.00

Total: 5,047.00kg 16,021.00.00Scenario Download (Execl)Submit order

Installation parameters

200KVA 3:3
Input parameter
Input voltage 380V AC
Input live conductor size 160mm2
Input neutral conductor size 160mm2
Input earth conductor size 160mm2
Input breaker 500A -3:3
Output parameter
Output voltage 380V AC
Output conductor size 150mm2
Output neutral conductor size 150mm2
Output earth conductor size 150mm2
Output breaker 400A -3:3
Battery specifications
External battery breaker 600A-3:3
External battery cable size 250mm2