Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

40KVA UPS — 30-minute backup configuration

Rated power
40KVA
Backup time
30 min
Kehua YTR3340

Matching UPS

Kehua YTR3340

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 40KVA 0.5 hour configuration scheme Y = 104
  • Host:Kehua YTR3340
  • Empty opening:NSX100F_DC_3P_100A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC16

    Quantity: 1
    Battery:Eaton ETNHF12-390WP

    Quantity: 1 group of 16 pieces
    Connection line:25 square battery connection line

    Quantity: 17
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Host:
  • Kehua YTR3340
  • Kehua UPS power supply
  • 1
  • 1*120.00kg
  • 320*840*867mm
  • 0.00
  • 0.00
  • Battery:
  • Eaton ETNHF12-390WP
  • Eaton Battery
  • Group 1    16 pieces
  • 16*28.50kg
  • 339*170*220mm
  • 0.00
  • 0.00
  • battery cabinet:
  • RC16
  • Love Pace
  • Group 1
  • 1*0.00kg
  • 828*499*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 16 only.
  • 2,820.00

Total: 577.60kg 3,937.00.00Scenario Download (Execl)Submit order

Installation parameters

40KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 10mm2
Input neutral conductor size 35mm2
Input earth conductor size 35mm2
Input breaker 80A -3P
Output parameter
Output voltage 380V AC
Output conductor size 10mm2
Output neutral conductor size 35mm2
Output earth conductor size 35mm2
Output breaker 100A -3P
Battery specifications
External battery breaker 200A-3P
External battery cable size 10mm2