UPS Runtime Configuration
160KVA UPS — 4-hour backup configuration

Matching UPS
Kehua YTR33160
Plan 1Long machine 160KVA 4 hours configuration scheme Y = 3333
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTR33160
- Kehua UPS power supply
- 1
- 1*320.00kg
- 600*900*1600mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 34 544 block
- 544*30.50kg
- 330*171*214mm
- 1,638.00
- 891,072.00
- battery cabinet:
- RC16
- Ruiwu
- Group 34
- 34*0.00kg
- 828*499*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 185 square battery connection line
- Ruiwu
- 545 root
- 545*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX400FDC
- Schneider Electric
- Group of 35
- 6.00kg
- 35*255*185*110mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 544 only
- 15,880.00
- Logistics transportation fee
- 8611.00
- 8611.00
- In-place fee
- 17322.00
- 17322.00
Total: 17,122.00kg 932,885.00.00Scenario Download (Execl)Submit order
Installation parameters
160KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 125mm2 |
| Input neutral conductor size | 125mm2 |
| Input earth conductor size | 125mm2 |
| Input breaker | 350A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 100mm2 |
| Output neutral conductor size | 100mm2 |
| Output earth conductor size | 100mm2 |
| Output breaker | 300A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 600A-Input AC 380V: Output AC 380V |
| External battery cable size | 200mm2 |