UPS Runtime Configuration
40KVA UPS — 2-hour backup configuration

Matching UPS
Kehua YTG3340
Plan 1Long machine 40KVA 2 hour configuration scheme Y = 230
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTG3340
- Kehua UPS power supply
- 1
- 1*400.00kg
- 800*500*1600mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 2 58.
- 58*30.50kg
- 330*171*214mm
- 1,638.00
- 95,004.00
- battery cabinet:
- No matching battery cabinet
- Group 2
- 2*0kg
- mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 25 square battery connection line
- Ruiwu
- 59 pieces
- 59*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_3P_100A
- Schneider Electric
- Group 3
- 1.60kg
- 3*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 58.
- 3,660.00
- Logistics transportation fee
- 1137.00
- 1137.00
- In-place fee
- 2374.00
- 2374.00
Total: 2,173.80kg 102,175.00.00Scenario Download (Execl)Submit order
Installation parameters
40KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 10mm2 |
| Input neutral conductor size | 35mm2 |
| Input earth conductor size | 35mm2 |
| Input breaker | 80A -3P |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 10mm2 |
| Output neutral conductor size | 35mm2 |
| Output earth conductor size | 35mm2 |
| Output breaker | 100A -3P |
| Battery specifications | |
| External battery breaker | 200A-3P |
| External battery cable size | 10mm2 |