UPS Runtime Configuration
300KVA UPS — 1-hour backup configuration

Matching UPS
Kehua YTG33300
Plan 1Long machine 300KVA 1 hour hour configuration scheme Y = 781
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTG33300
- Kehua UPS power supply
- 1
- 1*1830.00kg
- 1000*1600*1850mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 8 groups 256 block
- 256*30.50kg
- 330*171*214mm
- 1,638.00
- 419,328.00
- battery cabinet:
- RC32
- Ruiwu
- 8 groups
- 8*0.00kg
- 828*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 257 root
- 257*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- Group 9
- 0kg
- 9*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 256 only
- 10,120.00
- Logistics transportation fee
- 4869.00
- 4869.00
- In-place fee
- 9838.00
- 9838.00
Total: 9,638.00kg 444,155.00.00Scenario Download (Execl)Submit order
Installation parameters
300KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 250mm2 |
| Input neutral conductor size | 250mm2 |
| Input earth conductor size | 250mm2 |
| Input breaker | 800A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 200mm2 |
| Output neutral conductor size | 200mm2 |
| Output earth conductor size | 200mm2 |
| Output breaker | 630A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 1000A-Input AC 380V: Output AC 380V |
| External battery cable size | 375mm2 |