Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

60KVA UPS — 8-hour backup configuration

Rated power
60KVA
Backup time
8 h
Emerson UL33-0600L

Matching UPS

Emerson UL33-0600L

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 60KVA 8 hour hour configuration scheme Y = 1333
  • Host:Emerson UL33-0600L
  • Empty opening:NSX160F_DC_3P_160A

    Quantity: 15

    Battery DC switch cabinet
  • battery cabinet:No matching battery cabinet

    Number of: 14
    Battery:Ruiwu RW-G-12-100

    Quantity: 14 groups of 420 blocks
    Connection line:35 square battery connection line

    Quantity: 421
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 14    420 block
  • 420*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 687,960.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 420 only
  • 10,900.00

Total: 13,645.00kg 823,461.00.00Scenario Download (Execl)Submit order

Installation parameters

60KVA input AC 380V: output AC 380V
Input parameter
Input voltage 220V AC
Input live conductor size 25mm2
Input neutral conductor size 50mm2
Input earth conductor size 25mm2
Input breaker 150a -Input AC 380V: Output AC 380V
Output parameter
Output voltage 220V AC
Output conductor size 25mm2
Output neutral conductor size 50mm2
Output earth conductor size 25mm2
Output breaker 150a -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 300A-Input AC 380V: Output AC 380V
External battery cable size 50mm2