Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

3KVA UPS — 8-hour backup configuration

Rated power
3KVA
Backup time
8 h
APC SUA3000UXICH

Matching UPS

APC SUA3000UXICH

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 3KVA 8 hour hour configuration scheme Y = 500
  • Host:APC SUA3000UXICH
  • battery cabinet:RC4

    Number of: 5
    Battery:Ruiwu RW-G-12-100

    Quantity: 5 groups of 20 pieces
    Connection line:6 square battery connection line

    Number of: 21
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Host:
  • APC SUA3000UXICH
  • APC (Schneider Electric)
  • 1
  • 1*33.00kg
  • 432*196*544mm
  • 3,891.00
  • 3,891.00
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • 5 groups    20 yuan
  • 20*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 32,760.00
  • battery cabinet:
  • RC4
  • Ruiwu
  • 5 groups
  • 5*0.00kg
  • 499*499*572mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 20 only
  • 1,400.00

Total: 650.20kg 39,402.00.00Scenario Download (Execl)Submit order

Installation parameters

3KVA AC 220V input: AC 220V output
Input parameter
Input voltage 220V AC
Input live conductor size 4mm2
Input neutral conductor size 4mm2
Input earth conductor size 4mm2
Input breaker 16A -2P
Output parameter
Output voltage 220V AC
Output conductor size 4mm2
Output neutral conductor size 4mm2
Output earth conductor size 4mm2
Output breaker 16A -2P
Battery specifications
External battery breaker 63A-2P
External battery cable size 4mm2