Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

1KVA UPS — 8-hour backup configuration

Rated power
1KVA
Backup time
8 h
Emerson UHA1R-0010L

Matching UPS

Emerson UHA1R-0010L

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 1KVA 8 hour hour configuration scheme Y = 167
  • Host:Emerson UHA1R-0010L
  • battery cabinet:RC4

    Quantity: 1
    Battery:Ruiwu RW-G-12-100

    Quantity: 1 group of 4 pieces
    Connection line:6 square battery connection line

    Number of: 5
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 1    4 pieces
  • 4*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 6,552.00
  • battery cabinet:
  • RC4
  • Ruiwu
  • Group 1
  • 1*0.00kg
  • 499*499*572mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 4 only
  • 1,080.00

Total: 132.20kg 10,253.00.00Scenario Download (Execl)Submit order

Installation parameters

1KVA AC 220V input: AC 220V output
Input parameter
Input voltage 220V AC
Input live conductor size 2.5mm2
Input neutral conductor size 2.5mm2
Input earth conductor size 2.5mm2
Input breaker 10A -2P
Output parameter
Output voltage 220V AC
Output conductor size 2.5mm2
Output neutral conductor size 2.5mm2
Output earth conductor size 2.5mm2
Output breaker 10A -2P
Battery specifications
External battery breaker 32A-2P
External battery cable size 4mm2