Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

2KVA UPS — 2-hour backup configuration

Rated power
2KVA
Backup time
2 h
APC SRC2000UXICH

Matching UPS

APC SRC2000UXICH

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 2KVA 2 hour configuration scheme Y = 42
  • Host:APC SRC2000UXICH
  • battery cabinet:RC4

    Quantity: 1
    Battery:Ruiwu RW-G-12-38

    Quantity: 1 group of 8 pieces
    Connection line:6 square battery connection line

    Quantity: 9
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Host:
  • APC SRC2000UXICH
  • APC (Schneider Electric)
  • 1
  • 1*14.60kg
  • 175*432*457mm
  • 3,891.00
  • 3,891.00
  • Battery:
  • Ruiwu RW-G-12-38
  • Ruiwu
  • Group 1    8 pieces
  • 8*11.80kg
  • 197*165*170mm
  • 801.00
  • 6,408.00
  • battery cabinet:
  • RC4
  • Ruiwu
  • Group 1
  • 1*0.00kg
  • 499*499*572mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 8 only
  • 1,160.00

Total: 110.20kg 11,928.00.00Scenario Download (Execl)Submit order

Installation parameters

2KVA AC 220V input: AC 220V output
Input parameter
Input voltage 220V AC
Input live conductor size 2.5mm2
Input neutral conductor size 2.5mm2
Input earth conductor size 2.5mm2
Input breaker 10A -2P
Output parameter
Output voltage 220V AC
Output conductor size 2.5mm2
Output neutral conductor size 2.5mm2
Output earth conductor size 2.5mm2
Output breaker 10A -2P
Battery specifications
External battery breaker 40A-2P
External battery cable size 4mm2