UPS Runtime Configuration
6KVA UPS — 30-minute backup configuration

Matching UPS
Emerson GXE 06K00TL1101C00
Plan 1Long machine 6KVA 0.5 hour configuration scheme Y = 16
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson GXE 06K00TL1101C00
- Emerson
- 1
- 1*17.00kg
- 180*345*525mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-75W
- Eaton Battery
- Group 1 16 pieces
- 16*8.10kg
- 166*175*125mm
- 0.00
- 0.00
- battery cabinet:
- RC8
- Love Pace
- Group 1
- 1*0.00kg
- 828*499*572mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 6 square battery connection line
- Ruiwu
- 17 pieces
- 17*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX100F_DC_2P_50A
- Schneider Electric
- Group 1
- 1.20kg
- 1*161*70*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 1000.00
- 1 unit
- 1,000.00
- Battery installation fee
- 20.00
- 16 only.
- 1,320.00
- Logistics transportation fee
- 124.00
- 124.00
- In-place fee
- 348.00
- 348.00
Total: 147.80kg 1,792.00.00Scenario Download (Execl)Submit order
Installation parameters
6KVA AC 220V input: AC 220V output
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 4mm2 |
| Input neutral conductor size | 4mm2 |
| Input earth conductor size | 4mm2 |
| Input breaker | 32A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 4mm2 |
| Output neutral conductor size | 4mm2 |
| Output earth conductor size | 4mm2 |
| Output breaker | 32A -2P |
| Battery specifications | |
| External battery breaker | 75A-2P |
| External battery cable size | 6mm2 |