Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

60KVA UPS — 30-minute backup configuration

Rated power
60KVA
Backup time
30 min
Emerson Adapt-PM-60KVA-300K frame

Matching UPS

Emerson Adapt-PM-60KVA-300K frame

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 60KVA 0.5 hours configuration scheme Y = 62
  • Host:Emerson Adapt-PM-60KVA-300K Framework
  • Empty opening:NSX160F_DC_3P_160A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC40

    Quantity: 1
    Battery:Emerson (Vertiv)U12V230L/A

    Quantity: 1 group of 40 pieces
    Connection line:35 square battery connection line

    Number of: 41
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • battery cabinet:
  • RC40
  • Love Pace
  • Group 1
  • 1*0.00kg
  • 1002*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 40 only
  • 3,300.00

Total: 1,551.60kg 5,878.00.00Scenario Download (Execl)Submit order

Installation parameters

60KVA input AC 380V: output AC 380V
Input parameter
Input voltage 220V AC
Input live conductor size 25mm2
Input neutral conductor size 50mm2
Input earth conductor size 25mm2
Input breaker 150a -Input AC 380V: Output AC 380V
Output parameter
Output voltage 220V AC
Output conductor size 25mm2
Output neutral conductor size 50mm2
Output earth conductor size 25mm2
Output breaker 150a -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 300A-Input AC 380V: Output AC 380V
External battery cable size 50mm2