UPS Runtime Configuration
60KVA UPS — 1-hour backup configuration

Matching UPS
Emerson Adapt-PM-60KVA-300K frame
Plan 1Long machine 60KVA 1 hour hour configuration scheme Y = 125
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-60KVA-300K Framework
- Emerson
- 1
- 1*670.00kg
- 1200*1100*2000mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- Group 1 40 pieces
- 40*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- RC40
- Love Pace
- Group 1
- 1*0.00kg
- 1002*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 35 square battery connection line
- Ruiwu
- 41
- 41*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX160F_DC_3P_160A
- Schneider Electric
- Group 1
- 1.60kg
- 1*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 40 only
- 3,300.00
- Logistics transportation fee
- 956.00
- 956.00
- In-place fee
- 2012.00
- 2012.00
Total: 1,811.60kg 6,268.00.00Scenario Download (Execl)Submit order
Installation parameters
60KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 25mm2 |
| Input neutral conductor size | 50mm2 |
| Input earth conductor size | 25mm2 |
| Input breaker | 150a -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 25mm2 |
| Output neutral conductor size | 50mm2 |
| Output earth conductor size | 25mm2 |
| Output breaker | 150a -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 300A-Input AC 380V: Output AC 380V |
| External battery cable size | 50mm2 |