Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

100KVA UPS — 1-hour backup configuration

Rated power
100KVA
Backup time
1 h
Emerson eXM-100KVA

Matching UPS

Emerson eXM-100KVA

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 100KVA 1 hour hour configuration scheme Y = 208
  • Host:Emerson eXM-100KVA
  • Empty opening:NSX250F_DC_3P_250A

    Quantity: 3

    Battery DC switch cabinet
  • battery cabinet:RC40

    Quantity: 2
    Battery:Eaton ETNHF12-390WP

    Quantity: 80 pieces in 2 groups
    Connection line:95 square battery connection line

    Number of: 81
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Eaton ETNHF12-390WP
  • Eaton Battery
  • Group 2    80 yuan
  • 80*28.50kg
  • 339*170*220mm
  • 0.00
  • 0.00
  • battery cabinet:
  • RC40
  • Love Pace
  • Group 2
  • 2*0.00kg
  • 1002*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 80.
  • 6,600.00

Total: 2,715.70kg 10,924.00.00Scenario Download (Execl)Submit order

Installation parameters

100KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 120mm2
Input neutral conductor size 120mm2
Input earth conductor size 50mm2
Input breaker 250A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 380V AC
Output conductor size 95mm2
Output neutral conductor size 95mm2
Output earth conductor size 50mm2
Output breaker 200A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 200A-Input AC 380V: Output AC 380V
External battery cable size 95mm2