UPS Runtime Configuration
300KVA UPS — 30-minute backup configuration

Matching UPS
Emerson Adapt-PM-300KVA-400K frame
Plan 1Long machine 300KVA 0.5 hour configuration scheme Y = 312
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-300KVA-400K Framework
- Emerson
- 1
- 1*750.00kg
- 1400*1000*2000mm
- 0.00
- 0.00
- Battery:
- Eaton ETNHF12-390WP
- Eaton Battery
- Group 3 120 block
- 120*28.50kg
- 339*170*220mm
- 0.00
- 0.00
- battery cabinet:
- RC40
- Love Pace
- Group 3
- 3*0.00kg
- 1002*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 121 root
- 121*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- 4 groups
- 0kg
- 4*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 120 only
- 7,400.00
- Logistics transportation fee
- 2135.00
- 2135.00
- In-place fee
- 4370.00
- 4370.00
Total: 4,170.00kg 13,905.00.00Scenario Download (Execl)Submit order
Installation parameters
300KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 250mm2 |
| Input neutral conductor size | 250mm2 |
| Input earth conductor size | 250mm2 |
| Input breaker | 800A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 200mm2 |
| Output neutral conductor size | 200mm2 |
| Output earth conductor size | 200mm2 |
| Output breaker | 630A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 1000A-Input AC 380V: Output AC 380V |
| External battery cable size | 375mm2 |