Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

300KVA UPS — 8-hour backup configuration

Rated power
300KVA
Backup time
8 h
Emerson Adapt-PM-300KVA-400K frame

Matching UPS

Emerson Adapt-PM-300KVA-400K frame

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 300KVA 8 hour hour configuration scheme Y = 5000
  • Host:Emerson Adapt-PM-300KVA-400K Framework
  • Empty opening:No matching DC open

    Number of: 51

    Battery DC switch cabinet
  • battery cabinet:RC40

    Quantity: 50
    Battery:Ruiwu RW-G-12-100

    Quantity: 50 groups of 2000 blocks
    Connection line:No matching battery cable

    Quantity: 2001
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • 50 groups    2,000 yuan
  • 2000*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 3,276,000.00
  • battery cabinet:
  • RC40
  • Ruiwu
  • 50 groups
  • 50*0.00kg
  • 0*0*0mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 5000.00
  • 1 unit
  • 5,000.00
  • Battery installation fee
  • 20.00
  • 2000 only
  • 45,000.00

Total: 61,750.00kg 4,178,936.00.00Scenario Download (Execl)Submit order

Installation parameters

300KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 250mm2
Input neutral conductor size 250mm2
Input earth conductor size 250mm2
Input breaker 800A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 380V AC
Output conductor size 200mm2
Output neutral conductor size 200mm2
Output earth conductor size 200mm2
Output breaker 630A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 1000A-Input AC 380V: Output AC 380V
External battery cable size 375mm2