UPS Runtime Configuration
120KVA UPS — 8-hour backup configuration

Matching UPS
Ruiwu HF33120
Plan 1Long machine 120KVA 8 hour hour configuration scheme Y = 2000
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Ruiwu HF33120
- Ruiwu
- 1
- 1*285.00kg
- 600*778*1600mm
- 105,145.00
- 105,145.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 20 groups 800 block
- 800*30.50kg
- 330*171*214mm
- 1,638.00
- 1,310,400.00
- battery cabinet:
- RC40
- Ruiwu
- 20 groups
- 20*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 120 square battery connection line
- Ruiwu
- 801 root
- 801*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX400FDC
- Schneider Electric
- Group 21
- 6.00kg
- 21*255*185*110mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 800 only
- 21,000.00
- Logistics transportation fee
- 12456.00
- 12456.00
- In-place fee
- 25011.00
- 25011.00
Total: 24,811.00kg 1,474,012.00.00Scenario Download (Execl)Submit order
Installation parameters
120KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 120mm2 |
| Input neutral conductor size | 120mm2 |
| Input earth conductor size | 50mm2 |
| Input breaker | 250A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 95mm2 |
| Output neutral conductor size | 95mm2 |
| Output earth conductor size | 50mm2 |
| Output breaker | 200A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 200A-Input AC 380V: Output AC 380V |
| External battery cable size | 95mm2 |