UPS Runtime Configuration
6KVA UPS — 4-hour backup configuration

Matching UPS
Kehua YTR1106L
Plan 1Long machine 6KVA 4 hour configuration scheme Y = 125
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTR1106L
- Kehua UPS power supply
- 1
- 1*12.00kg
- 190*369*318mm
- 3,665.00
- 3,665.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 1 16 pieces
- 16*30.50kg
- 330*171*214mm
- 1,638.00
- 26,208.00
- battery cabinet:
- RC16
- Ruiwu
- Group 1
- 1*0.00kg
- 828*499*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 6 square battery connection line
- Ruiwu
- 17 pieces
- 17*0.00kg
- Standard
- 6.00
- 102.00
- DC air on:
- NSX100F_DC_2P_50A
- Schneider Electric
- Group 1
- 1.20kg
- 1*161*70*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 1000.00
- 1 unit
- 1,000.00
- Battery installation fee
- 20.00
- 16 only.
- 1,320.00
- Logistics transportation fee
- 301.00
- 301.00
- In-place fee
- 701.00
- 701.00
Total: 501.20kg 32,297.00.00Scenario Download (Execl)Submit order
Installation parameters
6KVA AC 220V input: AC 220V output
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 4mm2 |
| Input neutral conductor size | 4mm2 |
| Input earth conductor size | 4mm2 |
| Input breaker | 32A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 4mm2 |
| Output neutral conductor size | 4mm2 |
| Output earth conductor size | 4mm2 |
| Output breaker | 32A -2P |
| Battery specifications | |
| External battery breaker | 75A-2P |
| External battery cable size | 6mm2 |