UPS Runtime Configuration
100KVA UPS — 30-minute backup configuration

Matching UPS
Kehua YTG33100
Plan 1Long machine 100KVA 0.5 hour hour configuration scheme Y = 144
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTG33100
- Kehua UPS power supply
- 1
- 1*600.00kg
- 800*700*1800mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 1 29 pieces
- 29*30.50kg
- 330*171*214mm
- 1,638.00
- 47,502.00
- battery cabinet:
- No matching battery cabinet
- Group 1
- 1*0kg
- mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 95 square battery connection line
- Ruiwu
- 30 pieces
- 30*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX250F_DC_3P_250A
- Schneider Electric
- Group 1
- 1.90kg
- 1*161*105*86mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 29.
- 5,580.00
- Logistics transportation fee
- 793.00
- 793.00
- In-place fee
- 1686.00
- 1686.00
Total: 1,486.40kg 55,561.00.00Scenario Download (Execl)Submit order
Installation parameters
100KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 120mm2 |
| Input neutral conductor size | 120mm2 |
| Input earth conductor size | 50mm2 |
| Input breaker | 250A -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 95mm2 |
| Output neutral conductor size | 95mm2 |
| Output earth conductor size | 50mm2 |
| Output breaker | 200A -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 200A-Input AC 380V: Output AC 380V |
| External battery cable size | 95mm2 |







