UPS Runtime Configuration
200KVA UPS — 30-minute backup configuration

Matching UPS
Kehua YTG33200
Plan 1Long machine 200KVA 0.5 hours configuration scheme Y = 260
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Kehua YTG33200
- Kehua UPS power supply
- 1
- 1*1280.00kg
- 1000*1400*1850mm
- 0.00
- 0.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 3 96.
- 96*30.50kg
- 330*171*214mm
- 1,638.00
- 157,248.00
- battery cabinet:
- RC32
- Ruiwu
- Group 3
- 3*0.00kg
- 828*974*1112mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 240 square battery connection line
- Ruiwu
- 97.
- 97*0.00kg
- Standard
- 0.00
- 0.00
- DC air on:
- NSX630FDC
- Schneider Electric
- 4 groups
- 6.00kg
- 4*255*140*110mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 5000.00
- 1 unit
- 5,000.00
- Battery installation fee
- 20.00
- 96.
- 6,920.00
- Logistics transportation fee
- 2166.00
- 2166.00
- In-place fee
- 4432.00
- 4432.00
Total: 4,232.00kg 170,766.00.00Scenario Download (Execl)Submit order
Installation parameters
200KVA 3:3
| Input parameter | |
| Input voltage | 380V AC |
| Input live conductor size | 160mm2 |
| Input neutral conductor size | 160mm2 |
| Input earth conductor size | 160mm2 |
| Input breaker | 500A -3:3 |
| Output parameter | |
| Output voltage | 380V AC |
| Output conductor size | 150mm2 |
| Output neutral conductor size | 150mm2 |
| Output earth conductor size | 150mm2 |
| Output breaker | 400A -3:3 |
| Battery specifications | |
| External battery breaker | 600A-3:3 |
| External battery cable size | 250mm2 |